Buildings (Jun 2024)
Experimental Investigation on Cooling Performance of Water Spray Window
Abstract
The cooling performance of the energy-saving water spray window cooling system under summer conditions in Nanning city in southern China, is experimentally examined in this study. By constructing two identical test rooms for comparison, in the experiment we analyzed the effects of water temperature (22 °C, 26 °C, 30 °C), spray frequency (8, 10, 12, 15 min intervals), glass structure (single-layer, double-layer, triple-layer), air conditioning temperature (26 °C, 27 °C, 28 °C, 29 °C), and outer lamination thickness (30, 50, 100, 200 mm) on the cooling effect of windows, aiming to determine the optimal operating conditions. The experimental outcomes demonstrate that the appropriate operating mode for the water spray window system involves using the coldest water source (22 °C), with a spray interval of 8 min, a three-layer air cavity sprayed glass construction, an air cavity thickness set at 100 mm, and the best air conditioning temperature (26 °C). The study found that the water spray system can reduce the outer glass surface temperature of the window by 6 °C and the inner surface temperature by 2 °C. Moreover, the more glass layers and the thicker the lamination, the higher the energy saving rate; with a maximum energy saving rate of 35.19%. The water spray window has good adaptability and significant energy-saving effects in Southeast Asia. By scientifically selecting energy-saving glass types and fine-tuning operating modes, it is expected that efficient building energy conservation in hot climates can be achieved.