Energies (Jun 2023)

The Statistical Characteristics Analysis for Overvoltage of Elevated Transmission Line under High-Altitude Electromagnetic Pulse Based on Rosenblatt Transformation and Polynomial Chaos Expansion

  • Zheng Liu,
  • Dongwei Hei,
  • Congguang Mao,
  • Chuanbao Du,
  • Xin Nie,
  • Wei Wu,
  • Wei Chen

DOI
https://doi.org/10.3390/en16124622
Journal volume & issue
Vol. 16, no. 12
p. 4622

Abstract

Read online

A High-Altitude Electromagnetic Pulse (HEMP) could induce very fast transient overvoltage (VFTO) with nanosecond level rise time and mega-volt amplitude, which severely threatens the electrical devices connected to the elevated transmission line. An elevated transmission line with different locations may suffer different levels of HEMP threat since the dip angle could influence the polarization of the HEMP wave. The combination of Rosenblatt Transformation and Polynomial Chaos Expansion (R-PCE) is introduced in this paper. With this method, the efficiency of calculating the overvoltage of an elevated transmission line under HEMP is improved, speeding up 24.75 times. The influence of different factors (dip angle, elevated height, and earth conductivity) on the overvoltage of elevated transmission lines applied in power systems is calculated and analyzed. The numerical result shows with 99.9% confidence that the overvoltage would be over 3.7 MV of amplitude and 6.7 × 1014 V/s of voltage derivative, which is much more rigorous than a lighting pulse. We also find that elevated transmission lines may have a larger HEMP threat in a small dip angle area. The corresponding data are shown at the end of the paper, which could be useful for relative researchers in pulse injection experiments and reliable evaluation.

Keywords