The aim of this study is to improve the three-phase unbalanced voltage at the secondary side of a distribution transformer. The proposed method involves compensation sources injecting three different single-phase currents into the connected point of a grid. The computations of optimal single-phase currents are performed using the circuit analysis method and particle swarm optimization algorithm. An unbalanced three-phase power distribution system model is constructed, including a transformer Δ–Δ connection, V–V connection, load balance, load unbalance combination, and three single-phase compensation current sources. The results show that the voltage unbalance rate of the electricity user side is improved to less than 1%, and the three-phase total compensation apparent power is approximately 0 VA. In the future, the application of the model as an auxiliary service could be achieved by adding an energy storage system.