Zhongguo dianli (Oct 2020)

Optimization of Generator Arrangement for Jin-Zhong HVDC

  • Huifan XIE,
  • Yong MEI,
  • Jian ZHOU,
  • Guanghu XU,
  • Lei HUANG,
  • Ming LI,
  • Xiaobin ZHAO,
  • Jian YANG

DOI
https://doi.org/10.11930/j.issn.1004-9649.201805153
Journal volume & issue
Vol. 53, no. 10
pp. 180 – 186

Abstract

Read online

The paper proposes an optimization method which gives the minimum on-service generator number during the low-water and low-load period on the basis that the power system is safe and stable. The optimization considers three aspects, effective short circuit ratio, stability under island mode and low-order resonance. It is found that the introduction of active DC blocking during isolated operation mode can help effectively eliminate the risk of shortage of short-circuit current, power oscillations and low-order resonance. Operational practice suggests that the minimum on-service generator number of Liyuan and Ahai power plants can be reduced to two respectively when the proposed approach is applied. By reducing the on-service generator number, the risk of having generators operate without load during the low-water and low-load period is alleviated substantially, thus ensuring the safety of equipment of power plants during island mode.