Nonlinear Modeling and Transient Stability Analysis of Grid-Connected Voltage Source Converters during Asymmetric Faults Considering Multiple Control Loop Coupling
Abstract
As large-scale renewable energy sources are increasingly integrated into AC grids via voltage source converters (VSCs), the transient synchronization stability of phase-locked loop (PLL)-based VSCs during fault ride-through is gaining more attention. Most existing studies assume that the positive and negative sequence separation and current control dynamics are much faster than the PLL dynamics, thereby neglecting their impact on the transient synchronization stability of the system. However, when the PLL bandwidth is relatively large, ignoring the positive and negative sequence separation and current control dynamics may result in incorrect stability assessments. To address this issue, this paper first considers the multiple control loop coupling, including positive and negative sequence separation, current control, and PLL, to construct a full-order nonlinear mathematical model of the VSC grid-connected system under asymmetric fault conditions. Based on this, the phase trajectory method is employed to analyze the transient synchronization stability of the system. Additionally, this full-order mathematical model is used to determine the PLL bandwidth boundary beyond which the effects of positive and negative sequence separation and current control dynamics cannot be neglected. Finally, PSCAD/EMTDC simulation results validate the effectiveness of the theoretical analysis presented in this paper.