Applied Sciences (Feb 2018)

Conversion of a Direct to an Indirect Refrigeration System at Medium Temperature Using R-134a and R-507A: An Energy Impact Analysis

  • Rodrigo Llopis,
  • Daniel Sánchez,
  • Ramón Cabello,
  • Jesús Catalán-Gil,
  • Laura Nebot-Andrés

DOI
https://doi.org/10.3390/app8020247
Journal volume & issue
Vol. 8, no. 2
p. 247

Abstract

Read online

This work presents the experimental evaluation of energy consumption and refrigerant charge reduction when a commercial direct expansion refrigeration system is converted into an indirect system. The evaluation (with R-134a and R-507A) used a commercial cabinet with doors for medium temperature and a single-stage refrigeration cycle using a semi-hermetic compressor and electronic expansion valve; 24-h energy consumption tests were performed at laboratory conditions for each refrigerant and configuration at three heat rejection levels (23.3, 32.8 and 43.6 °C), maintaining an average product temperature inside the cabinet of 2 °C. The work analyses the impact of the conversion on temperature and pressure indicators, as well as, in the energy performance of each element. For R-134a the refrigerant charge was reduced in a 42.9%, but the energy consumption rose by 22.0%–22.8%; for R-507A the charge reduction was of 32.8% with an increase in energy consumption of between 27.7% and 38.7%.