An approach to suppress low-frequency oscillation in the hybrid multi-Infeed HVDC of mixed H2/H∞ robust-based control theory
Abstract
A hybrid multi-infeed HVDC (HMIDC) system is composed of line-commutated converter-based high-voltage direct current (LCC-HVDC) and voltage-source converterbased high-voltage direct current (VSC-HVDC), whose receiving ends have electrical coupling. To solve the problem of low-frequency oscillation (LFO) caused by insufficient damping in the HMIDC system, according to the multi-objective mixed H2/H∞ output feedback control theory with regional pole assignment, an additional robust damping controller is designed in this paper, which not only has good robustness, but also has strong adaptability to the change of system operation mode. In the paper, the related oscillation modes and transfer function of the controlled plant are obtained, which are identified by the total least squares estimation of signal parameters via rotary invariance technology (TLS-ESPRIT). In addition, the control-sensitive point (CSP) for suppressing LFO based on the small disturbance test method is determined, which is suitable for determining the installation position of the controller. The results show that the control sensitivity factor of VSC-HVDC is greater than that of LCC-HVDC so that adding an additional damping controller to VSC-HVDC is better than LCC-HVDC in suppressing the LFO of HMIDC. Finally, a hybrid double infeed DC transmission system with three receiving terminals is built on PSCAD/EMTDC where the time-domain simulations are performed to verify the correctness of the CSP selection and the effectiveness of the controller.
Keywords