Journal of Applied and Computational Mechanics (Apr 2022)

Heating Capacity of an Earth to Air Heat Exchanger in Arid Regions - Experimental Investigation

  • Nasreddine Sakhri,
  • Younes Menni,
  • Ali J. Chamkha

DOI
https://doi.org/10.22055/jacm.2020.31237.1843
Journal volume & issue
Vol. 8, no. 2
pp. 429 – 437

Abstract

Read online

Heating capacity of an earth to air heat exchanger EAHE equipped with an exterior fan in the arid region like the Southwest of Algeria is investigated experimentally. In-situ measurement of annual undisturbed subsoil vertical temperature profile is shown that it was 28°C at a depth of 1.5 meters. The EAHE made of 66 meters of PVC tube is demonstrated a heating capacity of 13°C and a cooling capacity of 7°C and a big dependence on local climate conditions. Great potentials and thermal comfort with less energy consumption are represented by earth to air or air-ground heat exchanger in the arid regions like the South of Algeria.