Zhejiang dianli (Nov 2022)

Analysis on protection configuration of AC/DC distribution networks

  • TONG Bin,
  • ZHAO Zhiyang,
  • ZHENG Shuting

DOI
https://doi.org/10.19585/j.zjdl.202211008
Journal volume & issue
Vol. 41, no. 11
pp. 52 – 60

Abstract

Read online

In view of the changes in the form of low-voltage distribution networks caused by the access of large-scale distributed generation (DG) and DC loads in the new power system, the protection and control of the distribution network under the new situation is studied. Firstly, this paper establishes a typical topology structure of a new distribution network with distributed generation and DC loads, and studies the transient characteristics on AC side and DC side, as well as the transient impedance characteristics during faults. Secondly, a new protection and configuration method and protection setting principle for low-voltage distribution networks under a new pattern is constructed based on transient characteristics. Finally, a new distribution network model is built using the MATLAB simulation platform to simulate the faults at typical locations of AC/DC distribution networks. It is verified that the proposed protection and control method has the advantages of accurate judgment and easy implementation.

Keywords