E3S Web of Conferences (Jan 2023)

Capacity Utilization Factor (CUF) of the 70kW on-grid solar station in the dry climate of Termez

  • Tursunov M. N.,
  • Sabirov Kh.,
  • Axtamov T. Z.,
  • Abdiyev U. B.,
  • Chariyev M. M.,
  • Yuldoshov B. A.,
  • Toshpulatov S. F.

DOI
https://doi.org/10.1051/e3sconf/202340102059
Journal volume & issue
Vol. 401
p. 02059

Abstract

Read online

The aim of the present study was to assess the installed capacity utilization factor and the suitability of a 70kW photovoltaic plant placed on the roof of a dormitory located at Termez city (Termez state university). We can report the energy to production directly through mobile devices. CUF is one of the quantities that shows the performance quality of each power generating station. The results of our research cover two months autumn and winter. Through this, the theoretically estimated minimum values of CUF on the least sunny days have also been proven in real values. It is estimated that the annual result of this value will be around 15%-20%. Because in the winter months, the value of individual CUF on open days increases by 20%. An estimated 15.68 mln kg of CO2 was avoided due to the generation of 22.4MWh of energy. This is a small improvement in the environment and energy sector.