Buildings (Sep 2024)

A Co-Location Study of 87 Low-Cost Environmental Monitors: Assessing Outliers, Variability, and Uncertainty

  • Sanyogita Manu,
  • Adam Rysanek

DOI
https://doi.org/10.3390/buildings14092965
Journal volume & issue
Vol. 14, no. 9
p. 2965

Abstract

Read online

While field research in indoor air quality (IAQ) increasingly uses large numbers of low-cost sensors, detailed validation of each sensor is becoming infeasible, ignored, or undeclared. Questions remain about whether these sensors meet manufacturer or third-party specifications and whether their utility improves with some validation, even under imperfect conditions. This study details the outcomes of a co-location experiment with 87 low-cost IAQ monitors, conducted with the objective of verifying their performance in measuring total volatile organic compounds (tVOCs), particulate matter 2.5 (PM2.5), carbon dioxide (CO2), temperature, and relative humidity. The monitors were installed next to professional-grade reference IAQ instruments in an office with controlled ventilation. A mixed validation methodology was used, involving outlier detection, uncertainty quantification, and performance metric calculations. Results showed that CO2, temperature, and humidity sensors reliably met manufacturer specifications, while tVOC sensors had significant accuracy issues, deviating by up to 79% from reference measurements—substantially more than the stated uncertainty of ±20%. PM2.5 sensors were more consistent but had an error margin of ±27%, compared to the stated ±15%. A total of 5 of the 87 sensors (5.7%) were outliers for at least one IAQ indicator. Despite the need for further long-term validation, this study highlights the importance of performing an experimental evaluation of low-cost IAQ monitors before field deployment.

Keywords