The Journal of Engineering (Apr 2019)
Electric field calculation and grading ring design for 750 kV four-circuits transmission line on the same tower with six cross-arms
Abstract
The transmission corridors can be effectively saved using 750 kV four-circuit transmission line on the same tower. In order to reduce the corona level, structure optimisation of fittings plays an important role in the transmission line design. In this study, the electric field distribution of 750 kV transmission line on six cross-arms tower was calculated based on finite element method, and the influences of pipe diameter, ring diameter and installation position of the grading ring were analysed. The results show that the increase of pipe diameter can reduce the electric field strength of grading ring while the increase of installation position and decrease of ring diameter are important to protect the end fitting of composite insulator. When using grading ring with the pipe diameter of 100 mm, the ring diameter of 700–900 mm and the installation position of 150–250 mm, the electric field strength can be controlled in a reasonable range. These results can provide references for the grading ring design of 750 kV four-circuit transmission line on the same tower.
Keywords