Microorganisms (Jul 2018)

Detection of Legionella Anisa in Water from Hospital Dental Chair Units and Molecular Characterization by Whole-Genome Sequencing

  • Giuseppe Fleres,
  • Natacha Couto,
  • Mariette Lokate,
  • Luc W. M. van der Sluis,
  • Christophe Ginevra,
  • Sophie Jarraud,
  • Ruud H. Deurenberg,
  • John W. Rossen,
  • Silvia García-Cobos,
  • Alex W. Friedrich

DOI
https://doi.org/10.3390/microorganisms6030071
Journal volume & issue
Vol. 6, no. 3
p. 71

Abstract

Read online

This study aims to assess contamination with Legionella spp. in water from dental chair units (DCUs) of a hospital dental ward and to perform its molecular characterization by whole-genome sequencing (WGS). We collect eight water samples (250 mL) from four DCUs (sink and water-syringe). Samples are tested for the presence of Legionella spp. (CFUs/mL) by culturing according to the Nederland Norm (NEN) 6265. Three DCUs are found positive for Legionella anisa, and four isolates are cultured (sink n = 2, water-syringe n = 1; two isolates from the same chair) with 1 × 102 CFU/mL. Whole-genome multi-locus sequence typing (wgMLST) results indicate that all strains belong to the same cluster with two to four allele differences. Classical culture combined with WGS allows the identification of a unique clone of L. anisa in several DCUs in the same hospital dental ward. This may indicate a common contamination source in the dental unit waterlines, which was fixed by replacing the chairs and main pipeline of the unit. Our results reveal tap water contamination in direct contact with patients and the usefulness of WGS to investigate bacterial molecular epidemiology.