Hemijska Industrija (Jan 2014)

Economizer water-wall damages initiated by feedwater impurities

  • Vidojković Sonja M.,
  • Onjia Antonije E.,
  • Devečerski Aleksandar B.,
  • Grahovac Nebojsa N.,
  • Nastasović Aleksandra B.

DOI
https://doi.org/10.2298/HEMIND130715082V
Journal volume & issue
Vol. 68, no. 5
pp. 559 – 563

Abstract

Read online

The main causes of efficiency loss in thermal power plants are boiler tube failures that diminish unit reliability and availability, and raise the cost of the electric energy. For that reason, regular examination of boiler tubes is indispensable measure for prevention future malfunctions of power units. Microscopic examination of economizer inner wall microstructure, analysis of chemical composition of deposit using x-ray diffraction (XRD) and scanning electron microscopy/energy dispersive spectroscopy (SEM/EDS) has been performed in a subcritical power plant. Stress corrosion cracking, pitting corrosion, destroyed protective magnetite layer, presence of magnetite and hematite in deposit and corrosive impurities within the cracks were indicated the effect of inadequate quality of feedwater that can not entirely ensure reliable operation of the boiler. It may be stated that maintenance of present boiler does not provide its reliable operation. Extensive chemical control of water/steam cycle was recommended. [Projekat Ministartsva nauke Republike Srbije, br. III 43009 i br. III 45012]

Keywords