MATEC Web of Conferences (Jan 2018)

Effect of indirect lightning strike to 66kV transmission line in Java-Bali system

  • Adi Kusuma Aristo,
  • Aditya Pramana Putu Agus,
  • S.D.A. Harsono Brian Bramantyo,
  • Sofiarto Munir Buyung

DOI
https://doi.org/10.1051/matecconf/201819711001
Journal volume & issue
Vol. 197
p. 11001

Abstract

Read online

Based on Java-Bali grid disturbance data, the 66kV transmission lines that is close to or intersect with 150kV or 500kV transmission line is often experienced earth fault due to insulator flashover. The insulator flashover can be caused by indirect lightning strike since lightning strikes tend to strike higher structure. Therefore, this paper will determine the effect of indirect lightning strike on 150kV or 500kV transmission line to 66kV transmission line by modeling and simulation using application of transient analysis. Variation of lightning peak current magnitude and gap between 66kV transmission line and transmission line with higher voltage is performed during simulation. The range of peak current magnitude follows the data from lightning detection systems, while the value of gap follows the data from actual condition. It is found that higher current peak and closer gap will cause higher transient overvoltage on insulator of 66kV transmission line thus insulator flashover may occur more frequent. Addition of earth wire on 66kV transmission line and gap between each transmission by organizing the sag of conductor can be performed to minimize the insulator flashover.