Tehnika (Jan 2015)

Reliability of supply of switchgear for auxiliary low voltage in substations extra high voltage to high voltage

  • Perić Dragoslav M.,
  • Tanasković Miladin R.

DOI
https://doi.org/10.5937/tehnika1506999P
Journal volume & issue
Vol. 70, no. 6
pp. 999 – 1004

Abstract

Read online

Switchgear for auxiliary low voltage in substations (SS) of extra high voltages (EHV) to high voltage (HV) - SS EHV/HV kV/kV is of special interest for the functioning of these important SS, as it provides a supply for system of protection and other vital functions of SS. The article addresses several characteristic examples involving MV lines with varying degrees of independence of their supply, and the possible application of direct transformation EHV/LV through special voltage transformers. Auxiliary sources such as inverters and diesel generators, which have limited power and expensive energy, are also used for the supply of switchgear for auxiliary low voltage. Corresponding reliability indices are calculated for all examples including mean expected annual engagement of diesel generators. The applicability of certain solutions of switchgear for auxiliary low voltage SS EHV/HV, taking into account their reliability, feasibility and cost-effectiveness is analyzed too. In particular, the analysis of applications of direct transformation EHV/LV for supply of switchgear for auxiliary low voltage, for both new and existing SS EHV/HV.

Keywords