IET Generation, Transmission & Distribution (Jul 2024)

Novel dual‐resonance damped alternating current testing system for offline partial discharge measurement of power cables

  • Li Wang,
  • Lei Jin,
  • Junbai Chen,
  • Hongjie Li

DOI
https://doi.org/10.1049/gtd2.13213
Journal volume & issue
Vol. 18, no. 14
pp. 2397 – 2405

Abstract

Read online

Abstract To accurately detect the early deterioration of electrical insulation in power cables, an energizing system is required for offline partial discharge (PD) measurements. The damped alternating current (DAC) testing system has emerged as an effective tool for inducing PD events. However, the existing systems often suffer from limitations such as signal interference, low sensitivity, and high costs. To address these issues, this study proposes a novel dual‐resonance DAC testing system that is simple in structure and cost‐effective. The prototype was built for testing 10‐kV distribution cables, and its effectiveness was validated through experimental tests on a cable sample. The results show that this approach significantly improves PD detection sensitivity and successfully completes PD localization. This research contributes to the development of more efficient and affordable DAC generation technology for power cable testing applications.

Keywords