Electrical engineering & Electromechanics (Sep 2014)

Research on electric potentials alignment on the ground surface within the grounding conductor territory

  • I.V. Nizhevskyi,
  • V.I. Nizhevskyi,
  • S.L. Shishigin

Journal volume & issue
no. 4
pp. 71 – 77

Abstract

Read online

Results of research on distribution of electric potentials on the earth surface in the territory with a grounding conductor are analyzed. It is shown that potential over the center of a square grounding conductor can be higher than that over the electrode. It is suggested to estimate the limit size of the cell of a complex net grounding conductor depending on the depth of its laying. It is found that a two-level design of the grounding conductor reduces touch voltage. Novelty of the results consists in application of a mathematical model to investigating electric characteristics of a two-level grounding conductor versus its laying depth.