Fault identification of double-circuit transmission lines on the same pole based on EEMD energy ratio
Abstract
In order to improve the sensitivity and reliability of traveling wave protection, on the basis of analyzing the relationship of the anti-traveling wave current amplitude in the window after the internal/external failure of the double circuit line on the same tower, a fault identification method based on EEMD energy ratio is proposed. Use EEMD decomposition to decompose the anti-traveling wave current in a time window after the fault into 7 scales, and extracts the EEMD energy ratio at each scale at both ends to form a feature vector. Then it is sent to the particle swarm optimization support vector machine (PSO-SVM) for training and testing, and the internal and external faults are identified. Experiments show that the algorithm has good fault identification ability, the fault accuracy is 95% and the method sensitivity is high.