AIP Advances (Jun 2024)

Research on propagation law of partial discharge ultrasonic signal in converter transformer

  • Hao Duan,
  • Lin Cheng,
  • Chuanxian Luo,
  • Jing Zhang,
  • Zhonghuan Su

DOI
https://doi.org/10.1063/5.0207346
Journal volume & issue
Vol. 14, no. 6
pp. 065023 – 065023-13

Abstract

Read online

When local discharge occurs inside the transformer, it will be accompanied by a burst sound to generate an ultrasonic signal, which can be used for fault monitoring and diagnosis inside the transformer. This paper focuses on studying the converter transformer and simulating and analyzing the location where local discharge is likely to occur in the converter transformer. The provided information includes the distribution of sound pressure within and outside the converter transformer and the impact of the winding on this distribution. Furthermore, the investigation focuses on the testing of local discharge in converter transformers using ultrasonic signals. A local discharge detection device for converter transformers has been developed. The experiment and analysis have been conducted, and what was learned was compared to the simulated outcomes. The determination of the local discharge position in converter transformers is based on the analysis of the time-varying waveform obtained at the observation point. This approach offers a novel method for finding and identifying local discharge.