Applied Sciences (Aug 2020)

Experimental and Numerical Investigation of the Internal Temperature of an Oil-Immersed Power Transformer with DOFS

  • Yunpeng Liu,
  • Xinye Li,
  • Huan Li,
  • Jiaxue Wang,
  • Xiaozhou Fan

DOI
https://doi.org/10.3390/app10165718
Journal volume & issue
Vol. 10, no. 16
p. 5718

Abstract

Read online

To accurately detect and monitor the internal temperature of an operating power transformer, the distributed optical fiber sensor (DOFS) was creatively applied inside an oil-immersed 35 kV transformer through high integration with the winding wire. On the former basis, the power transformer prototype with a completely global internal temperature sensing capability was successfully developed and it was also qualified for power grid operation through the ex-factory type tests. The internal spatially continuous temperature distribution of the operating transformer was then revealed through a heat-run test and the numerical simulation was also applied for further analysis. Hotspots of windings were continuously located and monitored (emerging at about 89%/90% height of low/high voltage winding), which were furtherly compared with the IEC calculation results. This new nondestructive internal sensing method shows a broad application prospect in the electrical equipment field. Also, the revelation of transformer internal distributed temperature can offer a solid reference for both researchers and field operation staff.

Keywords