Gong-kuang zidonghua (May 2013)

Analysis of relay protection action of grounding fault of no-load charging of a 330 kV transformer

  • LYU Bin,
  • NI Sai-sai,
  • LIU Yang,
  • ZHONG Li-na

Journal volume & issue
Vol. 39, no. 5
pp. 63 – 66

Abstract

Read online

In view of problem that a 330 kV start-up standby transformer took place relay protection action in no-load charging, the paper indicated that the action was caused by grounding fault of A-phase current transformer through analyzing charging current waveform recorded by electric quantity analyzer, and gave several suggestions to improve safety and reliability of charging test of large-scale transformer: strengthen insulation inspection for current and voltage transformers of high-voltage side of transformer; properly increase sensitivity of main and backup protection to prevent relay protection action by inrush current; it should record for three-phase current and voltage of high-voltage side of transformer in charging process.

Keywords