Molecules (Apr 2019)
Analysis of the Thermal Storage Performance of a Radiant Floor Heating System with a PCM
Abstract
This study first reviewed previous studies on floor heating systems based on the installation of a phase change material (PCM) and the current status of technical developments and found that PCM-based research is still in its infancy. In particular, the improvement of floor heat storage performance in indoor environments by combining a PCM with existing floor structures has not been subject to previous research. Thus, a PCM-based radiant floor heating system that utilizes hot water as a heat source and can be used in conjunction with the widespread wet construction method can be considered novel. This study found the most suitable PCM melting temperature for the proposed PCM-based radiant floor heating system ranged from approximately 35 °C to 45 °C for a floor thickness of 70 mm and a PCM thickness of 10 mm. Mock-up test results, which aimed to assess the performance of the radiant floor heating system with and without the PCM, revealed that the PCM-based room was able to maintain a temperature that was 0.2 °C higher than that of the room without the PCM. This was due to the rise in temperature caused by the PCM’s heat storage capacity and the emission of waste heat that was otherwise lost to the underside of the hot water pipe when the PCM was not present.
Keywords