Zhejiang dianli (Feb 2023)
Characteristic study on flue gas of a “three-in-one” indirect air cooling tower
Abstract
Different unit loads affect the flow heat transfer characteristics and flue gas diffusion of a “three-in-one” indirect air-cooling system. A numerical study is carried out on the tower of a 1 000 MW unit. The results show that as the load increases, the extraction effect and ventilation capacity of the tower at 100% load are 1.47 and 1.3 times higher than those at 50% load, respectively. Moreover, the cooling capacity of the tower is larger at higher loads. Load increase can reduce the concentration of SO2 on the inner wall of the air-cooling tower and raise the lift height of flue gas. At 100% load, the SO2 concentration is reduced by 4.55 mg/m3, and the maximum flue gas diffusion height is raised by up to 16.72 m compared to 50% load.