MATEC Web of Conferences (Jan 2018)
Research on the maximum fire smoke temperature beneath tunnel ceilings using longitudinal ventilation
Abstract
The maximum fire smoke temperature beneath tunnel ceilings using longitudinal ventilation was studied by both small-scale experiments and numerical simulations for a small heat release rate (HRR) fire. And then, the accuracy of the numerical simulation is verified. A numerical simulation is subsequently employed to modify the Kurioka model for cases in large HRR. Then, the modified Kurioka model is verified by various on-site high HRR fire experimental results conducted by other authors.