Energies (Nov 2022)

Improving the Efficiency of Earth Fault Detection by Fault Current Passage Indicators in Medium-Voltage Compensated Overhead Networks

  • Bartosz Olejnik,
  • Beata Zięba

DOI
https://doi.org/10.3390/en15239007
Journal volume & issue
Vol. 15, no. 23
p. 9007

Abstract

Read online

The article presents a method for detecting earth faults in a compensated medium-voltage network, which can be used especially in fault current passage indicators, but also in standard protection devices. The method is based on the adaptation process of the zero-sequence current protection setting, with the adaptation factor depending on the current value of the zero-sequence voltage. In this article, a comparative analysis of the classical and adaptive zero-sequence current criterion is conducted, taking into account the errors of the measuring system. The results of simulations performed in the PSCad environment are also presented. For a representative set of example short circuits, it was shown that the effectiveness of the presented criterion can be more than 50% higher than that of the standard criteria, taking into account the range of detected transition resistances. A comparison of the proposed method with admittance criteria was also drawn, and it was shown that it is suitable for the detection of high-resistance earth faults.

Keywords