Buildings (Jan 2024)

A Novel Model for Calculating Human-Body Angle Factor in Radiant Heat Transfer: Balancing Computation Accuracy and Speed

  • Yuyan Chen,
  • Yingdong He,
  • Nianping Li

DOI
https://doi.org/10.3390/buildings14020366
Journal volume & issue
Vol. 14, no. 2
p. 366

Abstract

Read online

With the growing interest in radiant heating and cooling systems, driven by their improved efficiency and enhanced thermal comfort compared to air systems, there is an increasing need to develop a more accessible method for designers to understand the implications of radiation heat exchange between the human body and radiant panels. To address this, a novel angle factor calculation model, named the HNU Angle Factor Model, was developed, taking into account the spatial arrangement and geometric relationship between the human body and radiant panels. The angle factors obtained using the HNU Angle Factor Model exhibited good agreement with the results obtained with Fanger diagrams and the contour integral method, with average relative differences of 8.1% and 10.0% for 140 cases, respectively. Furthermore, placing a radiant panel on the floor while maintaining its fixed size can contribute to the creation of an even and efficient thermal environment for individuals in both seated and standing positions. By implementing the HNU Angle Factor Model in practical engineering applications, more effective utilization of radiant systems can be achieved, as it provides an evaluation of the heat transfer between the human body and radiant panels.