MATEC Web of Conferences (Jan 2024)

Improved Over Current Relay (OCR) Coordination Using Time Multiple Setting (TMS)

  • Prasetijo Hari,
  • Fadli Ari,
  • Renaldi Feby

DOI
https://doi.org/10.1051/matecconf/202440202001
Journal volume & issue
Vol. 402
p. 02001

Abstract

Read online

Proper coordination between overcurrent relay (OCR) is needed to improve the reliability of the power distribution system. By choosing the proper time multiple setting (TMS), an optimum setting of OCR coordination can be achieved. This study improve working time coordination of OCR bay transformer using time multiple setting. Simulations were carried out to see the performance of the OCR bay transformer against a 3 phase short circuit on the 20 kV outgoing bus. The 3 phase short circuit was chosen because it produces the largest fault current among other types of short circuits. The discussion focuses on the OCR bay transformer, consist of OCR incoming 20 kV and OCR outgoing 150 kV. Existing data and calculation results were used as a parameter in the simulation. Simulation results with existing tms 0.21 and 0.23 for OCR incoming 20 kV and OCR outgoing 150 kV, respectively, have the potential to cause miscoordination of the OCR working time. Smaller short circuit current, bigger potential miscoordination. Resetting tms improves coordination of OCR bay transformer working time according to the standard used. Bigger value of tms, as long as it meets the standar, better OCR working time coordination to protect phase-phase fault current.