IET Generation, Transmission & Distribution (Apr 2024)

Analysis of fault current contributions from small‐scale single‐phase photovoltaic inverters and their impacts on the protection of electric power distribution systems

  • Lucas Rodrigues deAlmeida,
  • Rodrigo Nobis da Costa Lima,
  • José Rubens Macedo Junior

DOI
https://doi.org/10.1049/gtd2.13127
Journal volume & issue
Vol. 18, no. 7
pp. 1343 – 1359

Abstract

Read online

Abstract This paper presents an analysis of the fault current contributions of small‐scale single‐phase photovoltaic inverters under grid‐connected operation and their potential impact on the protection of distribution systems. To conduct this analysis, an autotransformer‐based voltage dip generator is proposed as a means to test the photovoltaic inverters' contribution to short‐circuit currents. Laboratory tests are then performed to obtain the short‐circuit current contribution of eight single‐phase photovoltaic inverters. Using the short‐circuit current data obtained, a behaviour model is developed and simulated on Matlab‐Simulink. The model is then applied to a real distribution system and case studies are conducted to simulate the potential impacts on the protection system. Results indicate that while the massive penetration of small‐scale single‐phase photovoltaic inverters can alter the protection system's operating time, the impacts are not significant. Only in very specific scenarios, such as events related to high impedance faults, some impact can be observed. In these situations, the presence of photovoltaic inverters further complicates the already difficult task of identifying high impedance faults through conventional overcurrent protections. This study provides valuable insights into the integration of photovoltaic inverters into distribution systems, and can aid in the development of effective protection measures for future grid designs.

Keywords