Shanghai Jiaotong Daxue xuebao (Sep 2024)

Online Monitoring Method for Inertial Support Capacity of Point-to-Grid in New Power Systems

  • DENG Xiaoyu, LIU Muyang, CHANG Xiqiang, NAN Dongliang, MO Ruo, CHEN Junru

DOI
https://doi.org/10.16183/j.cnki.jsjtu.2023.029
Journal volume & issue
Vol. 58, no. 9
pp. 1390 – 1399

Abstract

Read online

An accurate and timely monitoring for the inertia support capability of the point of interconnection of aggregated sources to the grid in a low-inertia new power system is crucial for the safety, stability, and economic operation of the system. In order to explain the basic idea of the online point-to-grid inertia monitoring method, the definition of inertia of power system based on the swing equation and existing online monitoring methods are analyzed. Then, in order to improve the accuracy of the existing online inertia monitoring method, an equivalent inertia constant identification method based on the regression method is developed. Combining the proposed inertia constant identification method with the online inertia monitoring method, a systematic method for online monitoring of the inertia support capacity of point-to-grid in new power system is developed based on synchronous phasor measurement units. Finally, the simulation analysis of a modified New England 10-machine 39-bus system proves the accuracy and the feasibility of the developed real-time inertia monitoring method for the new power system.

Keywords