The Journal of Engineering (Oct 2018)

Field measurement and verification of the UHF calibration platform based on the GTEM cell

  • Wang Yi-fan,
  • Gong Jin-long,
  • Jiang Jian-ling,
  • Tang Zhi-guo,
  • Wang Fei

DOI
https://doi.org/10.1049/joe.2018.8882

Abstract

Read online

The measurable electric field of the partial discharge ultra-high-frequency (PD UHF) detection system calibrated by a gigahertz transverse electromagnetic cell (GTEM) has been used as a key indicator to evaluate the performance of the detection system and regarded as the electric power standard. In this study, the sweep frequency and pulse signal were injected to the GTEM cell, and then the waveform and amplitude of the calibrated field strength were calculated by using the transfer function and voltage response of the monopole antennas. In the case of sweep frequency, comparing the measured result of the Narda field strength metre and the calculated result of monopole antennas, the error was found to be <8%, which verifies the correctness of the calibration of the monopole antennas to the steady-state electric field in the GTEM. In the case of pulse injection, comparing the simulation result of computer simulation technology and the calculated result of monopole antennas, the error of the peak of the field strength was found to be 1.7%, which verifies the correctness of the calibration of the monopole antennas to the pulse electric field in the GTEM.