Abstract

Read online

This study proposed an improved air conditioning design strategy based on building performance simulation for a stepped hall. The air velocity and air change rate of the case were measured on-site, which were compared with the simulation data to verify the reliability of the building simulation model. Then, the fully mixing ventilation scheme and the design schemes proposed in this study were simulated. Finally, the building simulation results were summarized to confirm the applicability of the air conditioning design strategy. The building performance results showed that the air distribution performance index (ADPI) value was 76.95% in the original case. Nevertheless, the effective draft temperature (EDT) in the middle seat area exceeded the standard value, indicating that a local cold shock would occur. Moreover, its scale for ventilation efficiency (SVE6) in the residential area was 2.54. However, the SVE6s in the other schemes were between 0.89 and 0.92. It means that the proposed schemes only needed to take one-third of the time to exhaust air. These three indicators’ visualization results can analyze the advantages and disadvantages of each scheme. Therefore, the improved building performance simulation strategy could inspect the design effect and give suggestions quickly for air conditioning design.