Energy Reports (Nov 2022)

Study on temperature rise characteristics of 110 kV XLPE cable under different service years considering dielectric loss

  • Sichen Qin,
  • Qiming Xu,
  • Qian Wang,
  • Jiawei Zhang,
  • Zeli Ju,
  • Zhe Hou,
  • Huan Lian,
  • Tao Wu,
  • Jingfan Zhang

Journal volume & issue
Vol. 8
pp. 493 – 501

Abstract

Read online

This paper studies temperature rise characteristics of 110 kV XLPE cable under different service years. When the load is 900 A, the maximum temperature of the cable under 0, 15 and 30 service years is 335.5 K, 372.96 K and 393.88 K respectively. Compared with the data obtained from non-aged cable, the temperature increase for samples operating for 15 and 30 years is 111.15% and 117.4% higher. For these samples, the proportion of heating due to cable dielectric loss is 2.77%, 25.45% and 34.78%. The research content of this paper provides a basis for the research on the optimal current carrying capacity of cables with different service years, provides a reference for the actual application of cables, and has guiding significance for the research on prolonging the service life of cables and improving the utilization rate of cable resources.