Renewable Energy and Environmental Sustainability (Jan 2018)

Utilization of air conditioner condenser as water heater in an effort to energy conservation

  • Sonawan Hery,
  • Saputro Panji,
  • Kurniawan Iden Muhtar

DOI
https://doi.org/10.1051/rees/2018001
Journal volume & issue
Vol. 3
p. 1

Abstract

Read online

This paper presents an experimental study of utilization of air conditioner condenser as water heater. Modification of existing air conditioner system is an effort to harvest waste heat energy from condenser. Modification is conducted in order to test the system into two mode tests, first mode with one condenser and second mode with two condensers. Harvesting the waste heat from condenser needs a theoretical and practice study to see how much the AC performance changes if modifications are made. It should also be considered how the technique of harvesting waste heat for water heating purposes. From the problem, this paper presents a comparison between AC performance before and after modification. From the experiment, an increase in compressor power consumption is 4.3% after adding a new condenser. The hot water temperature is attained to 69 °C and ready for warm bath. The increase in power consumption is not too significant compared to the attainable hot water temperature. Also seen that the value of condenser Performance Factor increase from 5.8 to 6.25 or by 7.8%.