Dynamic performance estimation of stator voltage regulator in rotary exciter system with DC exciter
Abstract
In this paper, procedure for AVR parameter estimation is proposed, based on step responses when synchronous generator in idle run. The exciter system includes AVR, thyristor rectifier and DC exciter. AVR is realized in the form of cascade control structure with two control loops. PID controller in the outer loop represents the primary controller. P controller in the inner loop represents secondary controller which enables the faster field current response time. The aim of procedure is to determine equivalent gain of PID controller and thyristor rectifier. The measurements used in the parameter estimation procedure are taken from fossil power plant 'Kolubara A', aggregate A5.