Atmosphere (Nov 2020)

Development of a Method to Determine the Fractional Deposition Efficiency of Full-Scale HVAC and HEPA Filter Cassettes for Nanoparticles ≥3.5 nm

  • Ana Maria Todea,
  • Frank Schmidt,
  • Tobias Schuldt,
  • Christof Asbach

DOI
https://doi.org/10.3390/atmos11111191
Journal volume & issue
Vol. 11, no. 11
p. 1191

Abstract

Read online

Novel methods have been developed to measure the fractional deposition efficiency for nanoparticles of full-scale HVAC and HEPA filter cassettes down to a particle size of 3.5 nm. The methods use a flame spray nanoparticle generator to produce NaCl test aerosols with narrow size distributions and very high concentrations. While the efficiency curves of lower efficiency filters of classes F7 and E10 were still able to be determined by measuring the size distributions of the polydisperse test aerosols upstream and downstream of the filter, two new testing procedures were developed for high efficiency filters of class H13. One considers the narrow size distributions of the test aerosols as quasi-monodisperse and follows a similar approach like EN 1822 for flat sheet media. The second one evaluates mobility classified fractions of the quasi-monodisperse test aerosols. A dedicated multiple charge correction scheme was developed to account for the effect of multiply charged particles. While the latter procedure allows to extend the particle size range, the prior significantly reduces the measurement time. All tests delivered meaningful results, which were very comparable with the results from flat sheet media tests.

Keywords