Energy Reports (Nov 2023)

Optimization method of PMU placements base on costs and risk assessments of state estimation

  • Weijun Lin,
  • Qingbin Wang,
  • Jingwei Long,
  • Zizhuo Lian,
  • Haoxian Liang,
  • Zhilin Liang

Journal volume & issue
Vol. 9
pp. 348 – 355

Abstract

Read online

In the context of vigorous development of new energy sources, optimizing the arrangement of phase measurement units (PMUs) is crucial to realize real-time data monitoring for distribution network (DN) condition assessment. Firstly, we propose a multi-objective model for optimal PMU placements. Secondly, we classified the buses based on the Jacobi matrix and the grid structure, and calculated the unobservable risk probability of the system by estimating the state of the PMUs installed on the buses, so as to obtain the observability of the system. Finally, two simulations of PMU placements in the DN implementing the IEEE39 bus are designed and the placement schemes are determined through solving the non-dominated Pareto solution sets by NSGA-II. The verifications show that the model reduces the placement number of PMUs, resulting in a cost reduction of 35.4% and an unobservable risk indicator δ reduction of 13.8%, and achieves an optimal placement of PMUs.

Keywords