Frontiers in Energy Research (Mar 2024)

Indirect lightning performance of 10-kV overhead distribution lines

  • Jianli Yu,
  • Jianli Yu,
  • Shanmao Gu,
  • Jianjun Liu,
  • He Liu

DOI
https://doi.org/10.3389/fenrg.2024.1367183
Journal volume & issue
Vol. 12

Abstract

Read online

The lightning-induced voltage in 10-kV overhead distribution lines was calculated and analyzed using the Agrawal coupling model and second-order finite difference-time domain (FDTD) method. The influence of lightning position on lightning-induced voltage was analyzed using the concept of indirect lightning withstanding levels. To achieve the limiting effect on lightning-induced voltage in 10-kV lines, the installation density of surge arresters should not be less than 1 group per 200–300 m.