International Journal of Air-Conditioning and Refrigeration (Oct 2024)
PMVd/PPDd model for predicting thermal comfort in air-conditioned buildings in hot and humid regions of Sub-Saharan Africa
Abstract
Abstract The model for predicting thermal comfort conditions established by Fanger remains widely used in scientific work, as a default means of in situ measurements. However, the use of Fanger data leads to dissatisfaction among users of air-conditioned buildings in humid tropical areas. This conclusion emerges from the work of Kemajou and al. (Cameroon) and Olissan and al. (Benin) in 2012, after survey studies on the judgments of thermal sensations of people occupying various air-conditioned spaces. This article develops a correction model for the Fanger model, by coupling the latter to models for predicting skin temperature and heat loss by evaporation of sweat through the skin, as well as to the skin thermal sensitivity of people active in a humid tropical climate. The model thus determined shows that the predicted optimal comfort temperatures are located in the range of 26.1 °C to 27.5 °C and better meets the expectations of the populations in this region. The respective differences with the investigations of Kemajou and al. and those of Olissan and al. are 0.40 °C and 0.55 °C. It also appears that the comfort humidity range is 30% to 80%, apart from any other safety measures.
Keywords