Sensors (Jun 2023)

Detection of Failures in Metal Oxide Surge Arresters Using Frequency Response Analysis

  • Tiago Goncalves Zacarias,
  • Rafael Martins,
  • Carlos Eduardo Xavier,
  • Julio Cezar Oliveira Castioni,
  • Wilson Cesar Sant’Ana,
  • Germano Lambert-Torres,
  • Bruno Reno Gama,
  • Isac Antonio dos Santos Areias,
  • Erik Leandro Bonaldi,
  • Frederico De Oliveira Assuncao

DOI
https://doi.org/10.3390/s23125633
Journal volume & issue
Vol. 23, no. 12
p. 5633

Abstract

Read online

This work presents an innovative application of Frequency Response Analysis (FRA) in order to detect early degradation of Metal Oxide Surge Arresters (MOSAs). This technique has been widely used in power transformers, but has never been applied to MOSAs. It consists in comparisons of spectra, measured at different instants of the lifetime of the arrester. Differences between these spectra are an indicator that some electrical properties of the arrester have changed. An incremental deterioration test has been performed on arrester samples (with controlled circulation of leakage current, which increases the energy dissipation over the device), and the FRA spectra correctly identified the progression of damage. Although preliminary, the FRA results seemed promising, and it is expected that this technology could be used as another diagnostic tool for arresters.

Keywords