High Voltage (Feb 2024)

Electromagnetic anisotropic homogeneous model for eddy‐current field in single‐phase wound core

  • Lijun Zhou,
  • Woyang Li,
  • Yingyi Xia,
  • Jiawei Chen,
  • Chenqingyu Zhang,
  • Xiaohu Cai,
  • Lei Guo,
  • Dongyang Wang

DOI
https://doi.org/10.1049/hve2.12387
Journal volume & issue
Vol. 9, no. 1
pp. 172 – 181

Abstract

Read online

Abstract The analysis of the eddy‐current field in the wound core widely used in the field of transformer energy conservation is taken as the theme. Adopting the homogenisation idea to consider the unique geometry of the wound core and features of its equivalent multi‐stage circular cross‐section magnetic boundary, a homogeneous model consisting of a columnar material with continuous homogeneous electromagnetic anisotropy is established by deriving the Maxwell equations of the magnetic quasi‐static field in the columnar coordinate system. Finally, a homogeneous fine element model for the eddy‐current field in the wound core is established and the accuracy of the model has been verified by the test platform. The result shows that the homogeneous model can be effectively used for the analysis of the eddy‐current field in the wound core, and the error of calculating the eddy‐current loss under different excitation conditions is less than 6% under the premise of extremely saving the engineering calculation cost, which will help improve the operational performance of the wound core and contribute to the energy‐saving goal of the high‐voltage equipment.