E3S Web of Conferences (Jan 2020)

Analysis on three typical abnormal microstructures of overhead power line suspension clamps

  • Liu Weike,
  • Zhou Mengbao,
  • Hu Jiarui,
  • Wu Songqi,
  • Cao Xianhui,
  • Xiong Jie,
  • Hu Lian,
  • Xie Yi,
  • Feng Chao,
  • Wang Jun,
  • Liu Chun

DOI
https://doi.org/10.1051/e3sconf/202016506029
Journal volume & issue
Vol. 165
p. 06029

Abstract

Read online

This article lists three typical abnormal microstructures of overhead power line suspension clamps, including inclusion, flake graphite and cementite network. A series of tests including macro check, hardness measurement, composition tests, Energy-dispersive x-ray analysis and metallographic observation have been carried out. The experimental results showed that the causes of abnormal microstructures mainly include: high content of impurities, flake graphite blank and unfulfilled annealing heat treatment. It is suggested to strengthen the supervision on suspension clamps before using, and focus on the quality inspection of metallographic structure and composition.