The integration of virtual power plants (VPP) has become more popular. Thus, research on VPP for different issues is highly desirable. This article addresses power quality issues. The presented investigation is based on multipoint, synchronic measurements obtained from five points that are related to the VPP. This article provides a proposition and discussion of using one global index in place of the classical power quality (PQ) parameters. Furthermore, in the article, one new global power quality index was proposed. Then the PQ measurements, as well as global indexes, were used to prepare input databases for cluster analysis. The mentioned cluster analysis aimed to detect the short-term working conditions of VPP that were specific from the point of view of power quality. To realize this the hierarchical clustering using the Ward algorithm was realized. The article also presents the application of the cubic clustering criterion to support cluster analysis. Then the assessment of the obtained condition was realized using the global index to assure the general information of the cause of its occurrence. Furthermore, the article noticed that the application of the global index, assured reduction of database size to around 74%, without losing the features of the data.