Frontiers in Energy Research (Jul 2024)

Transformer partial discharge location technology based on gradient oil temperature

  • Ruidong Yu,
  • Zhousheng Zhang

DOI
https://doi.org/10.3389/fenrg.2024.1428012
Journal volume & issue
Vol. 12

Abstract

Read online

IntroductionThe traditional partial discharge localization improvement strategy mainly starts from the intelligent algorithm, but fails to consider the influence of core winding and oil temperature on partial discharge positioning.MethodsThis paper also considers the influence of the iron core winding and oil temperature. Through finite element simulation, a transformer model was established to analyze the propagation characteristics of ultrasonic signals generated by partial discharge under the interference of gradient oil temperature and winding. The chaotic firefly-particle swarm hybrid algorithm is proposed, and through the calculation of Shubert’s multi-peak function. Finally, a partial discharge defect platform based on gradient oil temperature was built to verify the chaotic firefly-particle swarm hybrid localization algorithm.ResultsThe ultrasonic velocity generated by partial discharge in transformers cannot be fixed, and it is suggested that ultrasonic sensors should be installed near the center of the top of the transformer. The proposed algorithm can be better optimized in the case of multiple local extreme points. Under gradient oil temperature experiments, the algorithm achieves positioning errors less than 100 and 55 mm for cases with and without winding obstruction, respectively, with average positioning errors of 74.2 and 35.2 mm.DiscussionThe positioning method in this paper can provide a technical reference for the partial discharge positioning of transformers in actual operation.

Keywords