Energies (Jan 2018)

Dynamic Simulation of an Absorption Cooling System with Different Working Mixtures

  • Jesús Cerezo,
  • Rosenberg J. Romero,
  • Jonathan Ibarra,
  • Antonio Rodríguez,
  • Gisela Montero,
  • Alexis Acuña

DOI
https://doi.org/10.3390/en11020259
Journal volume & issue
Vol. 11, no. 2
p. 259

Abstract

Read online

High consumption of electricity represents an economic and social problem in warm places, caused by the massive use of cooling machines. Absorption systems are a sustainable method for air conditioning applications. However, environmental conditions should be analyzed to avoid crystallization problems of the working mixture. This article presents a thermal analysis of a solar absorption cooling system in dynamic conditions using NH3-H2O, H2O-LiBr, NH3-NaSCN, NH3-LiNO3, and H2O-LiCl working mixtures using Equation Engineering Solver (EES) and TRaNsient SYstem Simulation (TRNSYS) software. A solar collector area of 42.5 m2 was selected to carry out the thermal analysis. The results showed that H2O-LiCl obtained the maximum solar (0.67) and minimum heating (0.33) fraction. However, it obtained the maximum lost heat fraction (0.12), in spite of obtaining the best coefficient of performance (COP) among the other working mixtures, due mainly to a crystallization problem. The gain fraction (GF) parameter was used to select the adequate solar collector number for each working mixture. NH3-LiNO3 and NH3-H2O obtained the highest GF (up 6), and both obtained the maximum solar (0.91) and minimum heating (0.09) fraction, respectively, using 88.8 and 100.4 m2 of solar collector area, respectively.

Keywords