Tehnički Vjesnik (Jan 2017)

PSO based optimal distributed generation placement and capacity by considering harmonic limits

  • R. M. Sasiraja,
  • K. Muthulakshmi,
  • V. Suresh Kumar,
  • T. Abinaya

DOI
https://doi.org/10.17559/TV-20150430213846
Journal volume & issue
Vol. 24, no. Supplement 2
pp. 391 – 398

Abstract

Read online

Distributed Generation (DG) units are also called Dispersed Generation, Decentralized Generation and Embedded Generation. They are normally small generating plants, connected directly to either distribution side or customer side. The installation of inverter-based distributed generation (DG) has increased rapidly in recent years. This higher penetration level may result in the increased level of harmonics, which could exceed the permissible harmonic distortion level. The penetration level of DG is restricted by harmonic distortion, because of the nonlinear current injected by inverter based DG units. In this work, the maximum DG penetration level is determined, by considering the harmonic limits. The harmonics are determined by using the Decoupled Harmonic Power Flow (DHPF) approach. The constraints of this proposed problem include power balance equations, bus voltage limits, total and individual harmonic distortion limits specified by IEEE-519 standard. The problem is solved by using Particle Swarm Optimization (PSO) algorithm based optimization technique. Simulation results are obtained by MATPOWER/MATLAB in IEEE 30 and IEEE 57 bus test systems and the results prove the effectiveness of this proposed approach.