Cooling performance of Ceiling Radiant Textile Air Conditioning System with Ceiling Cassette Unit of Packaged Air Conditioner
Abstract
The authors developed a new radiant air conditioning system named ceiling radiant textile air conditioning system with ceiling cassette unit of packaged air conditioner (PAC). The nonflammable textile is stretched under the ceiling with ceiling cassette units of PAC with a distance of around 30 cm. The aim of this study is to investigate the cooling performance of this new radiant system, so the experiments with full scale model were conducted for three system. The first system is “textile only”, the second system is “textile with guide for air return grille” and the third system is “textile with guide and opening for air return grille”. Airflow rate through textile is measured by tracer gas method. In all cases, the vertical temperature distribution is almost uniform, and the cooling effect of “textile with guide and opening for air return grille” is the largest. As for the radiant effect, two systems of “only textile” and “textile with guide for air return grille” are superior to “textile with guide and opening for air return grille”. The airflow rate trough textile is doubled when using guide, and increased by five times if the opening was provided under the guide.