E3S Web of Conferences (Jan 2021)

Influence Analysis of Current Limiting Reactor on Pole-to-Pole Short Circuit Fault in DC Distribution System

  • Wang Zhenyu,
  • Wang Shouxiang,
  • Liu Qi,
  • Zhang Chunyu,
  • Zhao Qianyu,
  • Mu Hao

DOI
https://doi.org/10.1051/e3sconf/202125601032
Journal volume & issue
Vol. 256
p. 01032

Abstract

Read online

With the development of power electronic technology, flexible DC distribution system has gradually become a research hotspot. Pole-to-pole short circuit fault is the most serious fault type in DC distribution system. When pole-to-pole short circuit fault occurs in DC side, it will produce a large fault current, which will cause serious harm to DC distribution system. Therefore, it is urgent to install current limiting reactor to limit fault over-current. Aiming at the DC distribution system based on half bridge MMC, this paper analyses the fault mechanism and fault characteristics of pole-to-pole short circuit fault, studies the current limiting effect of the installation position and capacity of current limiting reactor on fault current, and carries out simulation verification in PSCAD / EMTDC platform. The analysis and simulation results show that installing a current limiting reactor at the outlet of the DC side can reduce the peak value of capacitor discharge current, and installing a current limiting reactor at the outlet of the AC side can reduce the overall amplitude of fault current.