Atmosphere (Dec 2022)

Climate Adaptability Analysis on the Shape of Outpatient Buildings for Different Climate Zones in China Based on Low-Energy Target

  • Youman Wei,
  • Siyan Wang,
  • Hongwei Dang,
  • Peng Liu

DOI
https://doi.org/10.3390/atmos13122121
Journal volume & issue
Vol. 13, no. 12
p. 2121

Abstract

Read online

Under the impact of COVID-19 and the needs for urban expansion, a large number of outpatient buildings have been rapidly constructed, but the problem of high energy consumption has always been ignored. There is a lack of research on the adaptability of building shape in different climate zones. Many studies have shown that a reasonable shape in the early stage of design can significantly reduce the energy consumption of buildings. Therefore, it helps if architects quickly select a reasonable shape that can effectively reduce energy consumption. This study summarized a number of outpatient building cases in China and proposed three typical building shapes: centralized-type (Shape-1), corridor-type (Shape-2), and courtyard-type (Shape-3). The Design Builder tool was used to simulate and analyze the typical building energy consumption in different climate zones. The simulation results show that Shape-2 (angle: 0°) should be chosen in severe cold zone; Shape-1 (angle: 90°) should be chosen in cold zone; Shape-1 (angle: 0°) should be chosen in hot summer and cold winter zone; Shape-1 (angle: 60°) should be chosen in hot summer and warm winter zone; and Shape-1 or Shape-2 can be chosen in warm zone. The results of this study can provide suggestions for the energy saving design of outpatient buildings in China and other areas with similar conditions. The result can help architects make rapid shape selection in the early stage of design.

Keywords