IET Generation, Transmission & Distribution (Feb 2024)

Electrical insulator defect detection with incomplete annotations and imbalanced samples

  • Fengqian Pang,
  • Chunyue Lei,
  • Jingsheng Zeng

DOI
https://doi.org/10.1049/gtd2.13107
Journal volume & issue
Vol. 18, no. 4
pp. 694 – 715

Abstract

Read online

Abstract Insulators are one of the key components in high‐voltage power systems that prevent transmission lines from grounding. Since they are exposed to different kinds of harsh environments and climates, periodic inspection is indispensable for the safety and high quality of power grid. Nowadays, unmanned aerial vehicle (UAV) inspection is more widely used, facilitating incorporation of convolutional neural network‐based detectors in the insulator detection task. However, these methods are generally based on the assumption that the image samples are balanced among different categories and possess completely ideal annotations. The problem of sample imbalance or incomplete annotation is rarely investigated in depth for insulator defect detection. Here, insulator defect detection with imbalanced data and incomplete annotations is focused on. The proposed framework, named Pi‐index, introduces positive unlabelled (PU) learning to solve the problem of incomplete annotation and designs a novel index the class prior, which is a key parameter in PU learning. Moreover, focal loss is integrated in our framework to alleviate the effect of sample imbalance. Experiment results demonstrate that the proposed framework achieves better performance than the baseline methods in situations of sample imbalance and missing annotation.

Keywords